Previous years GATE problems based on Two Wattmeter Method (Part 4)
1,181 plays

More
In this lesson I've discussed previous years GATE problems based on Two Wattmeter Method.

Pawan Chandani is teaching live on Unacademy Plus

Pawan Chandani
Faculty of GATE/ESE (Electrical Engineering) , Also a YouTuber and teaches Electrical Eng. subjects on YouTube | Jony Ive Award Winner

U
Unacademy user
sorry sir the query is in lesson 5
sir ques 17 ka answer galat h aapka -800 watt answer aaega iska
sir your videos are fentastic ,but we need english
Sir,at 3:00 , you have said that Vry is line voltage and line voltage leads the phase voltage by 30; shouldn't the statement be that phase voltage leads the line voltage by 30??...also Sir this condition of 30 degree phase between phase and line voltage is valid for a y connected load but how do we from the question that it's a star connected load??
RA
What will be the effect if we connect potential coil and current coil in series between B and Y in delta connection.
sir please upload reamining lectures.
Pawan Chandani
a year ago
measurements part 5 will be uploaded tomorrow....
Mir Shakeel
a year ago
thanku very much sir.
Mir Shakeel
a year ago
sir waiting.
Mir Shakeel
a year ago
sir reply
Pawan Chandani
a year ago
it has been uploaded
Mir Shakeel
a year ago
thanku sir
  1. Previous Year GATE problems based on Two Wattmeter Method By- Pawan Chandani


  2. Q 16. A single-phase is connected between R and Y terminals of a 415V, symmetrical, 3- phase, 4-wire system with phase sequence RYB. A wattmeter is connected in the system as shown in figure. The power factor of the load is 0.8 lagging. The wattmeter will read 0 o/


  3. Q 16. A single-phase load is connected between R and Y terminals of a 415V, symmetrical, 3-phase, 4-wire system with phase sequence RYB. A wattmeter is connected in the system as shown in figure. The power factor of the load is 0.8 lagging . The wattmeter will read o/ Ry 8N 0.8 Pa R N BN Ph , 30 L-6.86 100 100 L 36.86.


  4. W UPnx x cos (120'-(-6.86")) /00 . 5Cos (126.86) 0 x COS 597 W


  5. Q 17. The figure shows a three phase delta connected load supplied from a 400V, 50Hz, 30 balanced source. The pressure coil and current coil of a wattmeter are connected to the load as shown. With the coil polarities suitably selected to ensure a positive deflection The wattmeter reading will be 3- suppl C. C . . 50 Hz


  6. Q 17. The figure shows a three phase delta connected load supplied from a 400V, 50Hz, 30 balanced source. The pressure coil and current coil of a wattmeter are connected to the load as shown. With the coil polarities suitably selected to ensure a positive deflection. The wattmeter reading will be BR Suppl . . VL-120 ooV 50H2 = 8R YB V, L 120 400 20 -2I2o 100


  7. W yooxy cos (60'-120 )